Loading...

INTELLIGENT CO DETECTOR AND SOUNDER BASE

Sounder Base (45681- 800 ADV) is an analog/addressable combination carbon monoxide (CO) detector for use with Advanced fire alarm control panels. In addition to carbon monoxide monitoring, the CO detector and sounder base can accommodate any Advanced intelligent smoke, heat, or multi-sensor detector. For stand-alone CO detection, blank covers are available in low profile (45681-292) and high profile (45681-380) formats. The built in sounder of the Intelligent CO Detector and Sounder Base, can provide either a temporal 3 (fire alarm event) or temporal 4 (CO event) signal, with the fire alarm event having the highest priority. The sounder base requires a separate regulated 24 VDC supply whether from an Axis AX Notification Appliance Circuit (NAC) or from a Listed, supervised, power supply. In addition, common area sounder synchronization is possible with the MB-SDRT-SM, Synchronization Module.

  • Features:
    • Sounder Base CO and Alarm Temporal Patterns

    • Built-in Dedicated Microprocessor

    • UL 2075 & 2034 CO Monitoring Levels

    • Automatic & Manual CO Detector Testing

    • Sub-Addressing of Sounder Base

    • Integral Red Status LED

  • Listings and Approvals:
    • ETL ANSI/UL 864 Listed: 101564744NYM-001

    • UL268, 217, 2034, 2075: S2829

Model: 45681- 800 ADV


Share on :   Share on Facebook Share on Facebook
SPECIFICATIONS SPECIFICATIONS DESCRIPTION DESCRIPTION

Voltage

  • 24 VDC, UL864 Regulated

SLC Loop Current

  • Quiescent: 0.4 mA
  • Alarm : 0.7 mA
  • w/LED’s : 3.5 mA

Sounder 24 VDC Current

  • 0 mA Quiescent
  • 33mA Surge Current

Sounder Audible Intensity

  • 75 / 85dB @ 10 Feet

Wiring

  • Solid or Stranded; #12 to #22 AWG Terminals

Environment

  • Indoor, Dry

Operating Temperature

  • 32 o F-122 o F (0 o C-50 o C)

Humidity

  • 10-85% (Non-Condensing/Non-Freezing)

Material

  • Makrolon 6455 or 6555; 94V-0

Dimensions

  • 6” Diameter x 1.6”
DATA SHEET

45681-800ADV DATA SHEET