Loading...

REMOTE DISPLAY TERMINAL

The remote terminals utilize the same graphical LCD user interface that can be found on the Axis EN series fire panels and are based upon the same advanced, flash based, microprocessor technology. The Axis EN panels and remote terminals can communicate over the same 2-core network cable. They feature an integral network interface incorporating a special screen termination to prevent mains frequency earth-loop currents flowing between network nodes.

  • FEATURES:
    • The RCT has additional sector based control keys for Silence, Mute, Resound and Reset, which allows other networked panels to selectively respond to controls as programmed. E.g. on a site with multiple buildings, a user may be allowed to silence and reset fires originating in their own building. Fires originating from other buildings are displayed but cannot be reset.

    • Fully on-site programmable via on-board alphanumeric keypad or PC configuration tools.

    • View all information from across the network .

    • By using flash memory and an advanced graphical display the remote terminals can be easily configured to operate in virtually any language, with any character set and allows for the installer’s logo and company details to be displayed on the LCD display during normal operation.

    • Networked for System Display or Control

Model: MX-5020/30


Share on :   Share on Facebook Share on Facebook
SPECIFICATIONS SPECIFICATIONS DESCRIPTION DESCRIPTION

Display

  • White backlit 240x64 graphical LCD

LED Indicators

  • 2 red (1 x Fire, 1 x Alarm), 1 green (Power) & 3 amber (Fault & System)

Keypad

  • Alpha numeric keypad, navigation keys & on-board buzzer mute facility

Controls

  • System keys for Mute, reset, Silence, Resound

Key-Switch Input

  • Optional level 2 access enable key switch

Power Supply Input

  • 24 VDC, 115mA (/FT: 150mA) operating range 15-30V

External Supply Monitoring

  • Monitored external fault input

Number of Fire Zones

  • 2000

USB/Serial Ports

  • 1 x USB

Color

  • RAL 7035

Programming

  • Via on-board keypad or PC running Windows tools
DATA SHEET

MX-5020/30 DATA SHEET